Chapter 2-2 ELKO ELECTRICAL CODE
Section 2-2-5 ELECTRICAL CODE AMENDMENTS
All electrical construction work, electrical alterations or repair, installation and maintenance of
overhead and underground electrical supply and communication lines and the inspections thereof
shall be in conformity with the provisions of this Chapter and with the latest edition of the
National
Electrical Code along with supplements as adopted by the National Fire Protection Association
which is hereby adopted by the City, with the following specific additions and deletions:
ARTICLE 80 Administration and Enforcement is deleted in its entirety.
ARTICLE 210 Branch Circuits
Section 210.8 Ground-fault Circuit-interrupter Protection for Personnel
A new subsection (C) (1) to Section 210.8 is added to read as follows:
(C) All Occupancies
(1) All 125-volt, single-phase, 15 an 20 ampere receptacles installed
within 1.8 m (6ft) of sinks
or basins shall have ground fault circuit-interruptor protection for personnel.
Section 210.23 Permissible Loads
A new subsection (E) (1)-(7) to Section 210.23 is added to read as follows:
(E) Dwelling Branch Circuits
(1) The maximum number of outlets on a 15-ampere, 125-volt (nominal) circuit used exclusively
for receptacles shall be eight (8).
(2) The maximum number of outlets on a 20-ampere, 125-volt (nominal) circuit used exclusively
for receptacles shall be eleven (11).
(3) The maximum number of lighting outlets on a 15-ampere, 125-volt (nominal) lighting fixture
circuit shall be twelve (12) and not contain general purpose outlets.
Exception 1: Dedicated branch circuits feeding only IC rated recessed fixtures may use Article
220.3 (B)(4) for maximum number of lighting outlets.
Exception 2: In branch circuits serving smoke detectors outlets need not be counted with the
other lighting outlets.
Exception 3: Designed plans by a Nevada Registered Electrical Engineer.
(4) The maximum number of lighting outlets on a 20-ampere, 125-volt (nominal) lighting fixture
circuit shall be sixteen (16) and not contain general purpose outlets.
Exception 1: Dedicated branch circuits feeding only IC rated recessed fixtures may use Article
220.3 (B)(4) for maximum number of lighting outlets.
Exception 2: In branch circuits serving smoke detectors outlets need not be counted with the
other lighting outlets.
Exception 3: Designed plans by a Nevada Registered Electrical Engineer.
(5) The maximum number of outlets on a 15-ampere, 125-volt (nominal) circuit used either
exclusively for receptacles, for lighting outlets or for any combination of receptacles and lighting
outlets shall be eight (8).
Exception 1: Dedicated branch circuits feeding only IC rated recessed fixtures may use Article
220.3 (B)(4) for maximum number of lighting outlets.
Exception 2: In branch circuits serving smoke detectors outlets need not be counted with the
other lighting outlets.
Exception 3: Designed plans by a Nevada Registered Electrical Engineer.
(6) The maximum number of outlets on a 20-ampere, 125-volt (nominal) circuit used either
exclusivley for receptacles, for lighting outlets or for any combination of receptacles and lighting
outlets shall be eleven (11).
Exception 1: Dedicated branch circuits feeding only IC rated recessed fixtures may use Article
220.3 (B)(4) for maximum number of lighting outlets.
Exception 2: In branch circuits serving smoke detectors outlets need not be counted with the
other lighting outlets.
Exception 3: Designed plans by a Nevada Registered Electrical Engineer.
(7) No more than four (4) duplex receptacle outlets serving the required counter top receptacles
shall be installed on any small appliance branch circuit.
Exception 1: Receptacles installed to provide power for electric ignition systems or clock timers
for gas-fired ranges, ovens or counter-mounted cooking units.
Exception 2: Designed plans by a Nevada Registered Electrical Engineer.
ARTICLE 225 - OUTSIDE BRANCH CIRCUITS AND FEEDERS
Section 225.32 Location is amended by deleting "either
inside or" from the first sentece
Section 225.31. Dissconnecting Means is amended by adding the following
to the end:
When more than one building or other structure is on the same property and under
single
management, each building or other structure served shall be provided with means for
disconnecting all ungrounded conductors. The disconnecting means shall be installed outside of
the building served at a readily accessible location. A shunt trip may be used to satisfy this
requirement where:
(1) It is located at seven (7) feet above finished grade.
(2) It is located within a twelve (12) inch equilateral triangle, red in color.
ARTICLE 230 - SERVICES
Subsection 230.70(A) Location - (1) and (2) are deleted in their
entirety and new Subsections
(1) and (2) are added to read as follows:
(A) The service disconnecting means shall be installed
at a readily accessible location
outside of a building or structure. A shunt trip may be used to satisfy this requirement where:
(1) It is located at seven (7) feet above finsihed grade.
(2) It is located within a twelve (12) inch equilateral triangle red in
color.
ARTICLE 310 - CONDUCTORS FOR GENERAL WIRING
Section 310.5 Minimum Size of Conductors is deleted in its entirety and
a new Section 310.5 is
added to read as follows:
310-5. Minimum Size of Conductors. The minimum size of conductors shall be as shown in Table
310-5.
|
|
Minimum Conductor
size
(AWG)
|
|
Conductor
Voltage Rating
|
Copper
|
Aluminum or
Copper-Clad
Aluminum*
|
|
0-2000
|
14
|
6
|
|
2001-8000
|
8
|
6
|
|
8001-15,000
|
2
|
2
|
|
15,001-28,000
|
1
|
1
|
|
28,001-35,000
|
1/0
|
1/0
|
Aluminum and Copper-Clad Aluminum conductors smaller than No. 6 AWG shall not be used.
ARTICLE 334 - NONMETALLIC-SHEATHED CABLE
Section 334-12 (A). Uses not permitted.
Section 334.12 (A) is amended by adding two new Subsections (11) and (12) to
read as
follows:
(11) In Type I or Type II construction as defined in the Building Code.
(12) In any industrial or commercial occupancy including motels and hotels.
ARTICLE 340 - UNDERGROUND FEEDER AND BRANCH-CIRCUIT CABLE
Section 340.12 Uses not Permitted
Section 340.12 is amended by adding a new Subsection (12) to read as follows:
(12) In or on any industrial or commercial occupancy including motels and hotels.
(Ord. 667, Amended, 07/11/2006, Prior Text; Ord. 637, Repealed and Replaced, 09/27/2005, Prior Text)